The flash point is the lowest temperature at which a liquid gives off enough vapour to ignite near its surface. Fire codes, including NFPA 30 and the National Fire Code of Canada, use it to sort liquids into classes:
| Class | Flash point | Fire code term |
|---|---|---|
| I (IA, IB, IC) | Below 37.8 °C (100 °F) | Flammable |
| II | 37.8 to below 60 °C (100 to below 140 °F) | Combustible |
| IIIA | 60 to below 93 °C (140 to below 200 °F) | Combustible |
| IIIB | 93 °C (200 °F) and above | Combustible |
Class I is subdivided further by flash point and boiling point. Common lab examples include acetone, ethanol, methanol, hexane, toluene and diethyl ether.
WHMIS labels and safety data sheets use a different scheme, with flammable liquid categories that extend to higher flash points. A liquid labelled flammable on its SDS may be a combustible liquid under the fire code, so check both when planning storage.
Classification drives practical requirements: how much may be kept in a lab, when an approved storage cabinet with self-closing doors is needed, ventilation, control of ignition sources and the use of refrigerators designed for flammable storage. NFPA 45 adds limits based on the lab's fire hazard class. The local fire authority and the organization's EHS office set the final rules.
See flammable liquid storage cabinets, chemical segregation and the flammable liquids cabinet.