Cleanrooms involve many trades in a small space: architecture, air handling, filtration, lighting, controls, doors, windows, utilities and furniture. When each is bought separately, the gaps between them become the owner's problem. Design-build puts one team in charge from requirements to handover.
We design and build modular hardwall and softwall cleanrooms for hospital pharmacies, medical device assembly, electronics, life science labs and other controlled processes. Projects range from a single softwall enclosure to a suite of rooms with gowning, airlocks and a pressure cascade.
What the service covers
- Requirements. Turning your process into a user requirements specification with the class or grade, room conditions and operating patterns.
- Classification. Choosing an ISO 14644-1 class and, where relevant, a GMP grade under EU/PIC/S GMP Annex 1. Our ISO classes guide explains the options.
- Layout and flow. Separate routes for people, materials and waste, gowning rooms, airlocks and the pressure cascade between rooms.
- Air systems. Air change rates, filter coverage with fan filter units or ducted HEPA supply, return air paths, temperature, humidity and pressure control.
- Shell and components. Wall and ceiling systems, coving, flooring, flush windows, doors, pass-through chambers, sealed lighting and pressure monitors from our cleanroom range.
- Furniture. Stainless work tables, gowning benches, garment cabinets and scrub sinks.
- Pharmacy compounding. Rooms laid out to the NAPRA model standards, which draw on USP 797 and USP 800. See our pharmacy compounding cleanroom layout.
HVAC and structural design is carried out or sealed by professional engineers licensed in the province of the project. The owner's engineer of record, quality team and the local authority having jurisdiction approve the design, and an independent certifier tests the finished room.
How it works
- User requirements. We document the process, class or grade, room conditions, equipment, staffing and cleaning regime.
- Concept. We lay out rooms, flows and pressures, and choose between softwall, hardwall or a mix.
- Design development. We complete architectural, HVAC, electrical and utility design and coordinate it in one model.
- Reviews and approvals. You and your quality team review the design. We support the building permit and any regulatory submissions you make.
- Fabrication and installation. Panels, ceilings, filters and components are built and installed in a planned sequence, followed by a cleanroom clean.
- Commissioning and testing. We balance the air system and verify pressures and alarms. An independent certifier then carries out airflow, filter integrity and particle count testing to ISO 14644.
- Handover and training. We train your staff on operation, monitoring, cleaning and filter care.
What you receive
- User requirements specification review
- Layout drawings showing room classes, pressures and personnel and material flows
- Room data sheets
- HVAC calculations for air changes, filter coverage and pressurization
- Architectural, mechanical and electrical drawings
- Equipment and component submittals
- Commissioning plan and records, with support for installation and operational qualification
- Operation and maintenance manuals, cleaning guidance and as-built drawings
Typical projects
- A hospital pharmacy upgrading its sterile compounding rooms
- A medical device maker adding an ISO 7 assembly room
- A research lab adding a small ISO 7 or ISO 8 room for clean processing
- An electronics company installing a softwall enclosure over a single process tool
- A cell therapy group planning a suite with Grade B and Grade C rooms
Good to know
Every step up in cleanliness adds air, filters and running cost. A clear requirements document is the best way to avoid over-specifying. Our guide to cleanroom budget planning explains what drives cost.
To start planning a cleanroom, request a consultation.