A lab module is the basic building block of a lab floor plan. In its common form, it is the width needed for a bench on each side of a working aisle, plus the wall or service zone, repeated along a building. Module widths often fall around 3.2 to 3.4 m (about 10½ to 11 ft), with depths commonly in the range of 6 to 9 m (about 20 to 30 ft), but each project sets its own.
A typical width breaks down like this:
- Two benches about 750 mm (30 in) deep.
- An aisle of about 1.5 m (5 ft) between them.
- Space for partitions, chases and tolerances.
Why plan on a module:
- Flexibility: labs can be enlarged, divided or reassigned in whole modules without moving structure or main services.
- Coordination: structural grid, ceiling, lighting, ductwork and service chases all line up.
- Predictability: repeated modules make costs, fume hood counts and services easier to estimate.
Half modules are often used for write-up areas, equipment alcoves or support rooms.
See lab modules: planning on a grid, aisle widths and clearances, or sketch a module in the lab planner.