LaboratoryEquipment.caCasework · Fume hoods · Cleanrooms Placeholder data
Glossary

Particle count

A measurement of the number of airborne particles in a volume of air, by size, used to classify and monitor cleanrooms.

Particle counts are taken with a discrete particle counter, an instrument that draws a known flow of air through a light beam and sizes each particle by the light it scatters. Common portable counters sample 28.3 L/min (1 cfm), with higher-flow models available, and report counts in several size channels such as 0.3, 0.5, 1.0 and 5.0 µm.

Results are expressed as particles per cubic metre at or above each size, and compared with the limits for the target ISO class. For formal classification, ISO 14644-1 sets the minimum number of sample locations from the room's floor area and a minimum sample volume at each location.

Particle counting serves two purposes:

  • Classification and certification: tests that confirm the room meets its class, typically at handover and then on a regular schedule.
  • Monitoring: routine or continuous counts that catch problems between certifications, sometimes with fixed sensors wired to alarms.

A particle counter does not distinguish living from non-living particles. Microbial monitoring uses separate methods such as active air samplers, settle plates and contact plates.

Counts usually rise when people are present and working, which is why gowning discipline and traffic control matter as much as filtration.

See cleanroom certification and monitoring and designing a gowning room.