Airlock

A small room with doors at each end, placed between spaces of different cleanliness or containment to control airflow and contamination.

An airlock is a buffer between two spaces. People or materials enter, the first door closes, and only then does the second door open. That sequence, together with controlled air pressures, stops air and contamination from flowing straight through.

Airlocks are classed by their pressure relative to the rooms on either side:

  • Cascade: pressure between the two rooms, so air flows from the cleaner side through the airlock to the less clean side. A common type in cleanrooms.
  • Bubble: higher pressure than both sides, pushing air outward in both directions. Used where a clean area must be protected and a contained room's air must not escape to the corridor.
  • Sink: lower pressure than both sides, drawing air in from both directions. Used where hazardous material must be contained.

Airlocks are also described by use: personnel airlocks, which often double as gowning rooms, and material airlocks for carts and equipment.

Design points:

  • Door interlocks so only one door opens at a time.
  • A visible pressure differential display at each door.
  • Enough size for the largest cart or equipment, and enough floor area for gowning where needed.
  • Time for pressure to recover between door openings.

See pressure cascades and airlocks and designing a gowning room.