Pressure differential

The difference in air pressure between two adjacent spaces, used to make air flow from cleaner to less clean areas or to keep hazards contained.

Air moves from higher pressure to lower pressure. Designers use that to control where contamination goes. Pressure differential is measured in pascals (Pa), or in inches of water column in older documents.

How it is used:

  • Cleanrooms are kept at higher pressure than adjoining less clean areas, so air leaks outward through door gaps and openings rather than in. A commonly used step between adjacent rooms of different classes or grades is 10 to 15 Pa (about 0.04 to 0.06 in w.c.).
  • Chemical labs are kept slightly negative to corridors, usually by exhausting more air than is supplied, so fumes do not escape into public areas.
  • Containment rooms, such as CL3 labs and hazardous drug compounding rooms, are kept negative so air flows inward.

Several rooms in sequence, each at a different pressure, form a pressure cascade. Airlocks between them keep the steps stable when doors open.

What it takes to hold a pressure differential:

  • Tight construction: sealed walls, ceilings, penetrations and doors.
  • Supply and exhaust controls that respond to door openings and filter loading.
  • A room pressure monitor at each critical door, with alarms that use a short delay so normal door openings do not trigger them.

The facility's engineer and quality or biosafety lead set the actual values. See pressure cascades and airlocks and makeup air.