Capture velocity applies to local exhaust devices that sit outside the source: snorkel arms, slot hoods along a bench edge, canopy hoods and downdraft tables. Unlike a fume hood, which encloses the work, these devices must reach out and pull contaminated air toward them. The capture velocity is the air speed they must create at the source to overcome the contaminant's own motion and any room air currents.
Air velocity falls off steeply with distance from an open inlet. For a plain round opening, velocity on the centreline about one diameter away is already down to roughly a tenth of the velocity at the opening. Doubling the distance from the source therefore needs far more than double the airflow.
Published design ranges start around 0.25 to 0.5 m/s (50 to 100 fpm) for vapours released with little velocity into still air, and rise steeply for hot, energetic or high-velocity sources.
Practical points:
- Put the inlet as close to the source as the work allows, ideally within one inlet diameter.
- A flange around a snorkel or slot inlet improves capture for the same airflow.
- Keep supply diffusers and doors from blowing across the capture zone.
Compare with face velocity, which describes airflow through the opening of an enclosing hood. For hazardous chemicals, a full fume hood usually gives better containment; see how a laboratory fume hood works.