Exhaust stack

The vertical discharge of a lab exhaust system, designed to throw contaminated air high and fast enough to clear the building and its air intakes.

The exhaust stack is where fume hood exhaust leaves the building. Its job is to get contaminants into the free air stream above the roof so they disperse, rather than wrap around the building and come back in through air intakes, doors or windows.

Good stack practice is well established:

  • Discharge straight up. Rain caps that deflect air downward defeat the purpose; use designs that keep rain out without blocking upward flow.
  • Height: guidance commonly calls for discharge at least 3 m (10 ft) above the adjacent roof, and higher where nearby buildings, rooftop equipment or intakes demand it.
  • Exit velocity: a high discharge velocity, commonly around 15 m/s (3,000 fpm), helps the plume rise clear of the building's wake.
  • Fans at the roof: placing fans at the end of the duct run keeps ducts inside the building under negative pressure, so leaks draw air in rather than push fumes out.

Wind, building shape and neighbouring structures make stack design site-specific. On complex sites, engineers use dispersion modelling or wind tunnel studies to confirm intakes stay clear. The engineer of record decides the final design.

Some exhaust needs its own dedicated duct and stack, such as hoods used for perchloric acid. See exhaust ducts, fans and stacks and our engineering services.