Every litre of air a fume hood exhausts has to be replaced. Makeup air is that replacement supply. In most chemical labs it is 100% outdoor air, because recirculating lab air to other spaces would spread contaminants. It must be filtered, heated in winter, and cooled and dehumidified in summer, which makes makeup air one of the largest energy costs in a lab building, especially in Canadian climates.
Labs are usually supplied with slightly less air than they exhaust. The difference, called the offset, keeps the lab at a slightly negative pressure differential relative to the corridor, so air flows into the lab and not out.
How makeup air enters the room matters as much as how much there is. Supply diffusers that throw air at high velocity near a hood create cross drafts that can pull fumes out of the sash opening. A common design goal keeps air velocities near the hood face well below the face velocity. Low-velocity diffusers placed away from hoods and doors help.
Signs of a makeup air problem:
- Doors that are hard to open or slam shut.
- Whistling at door gaps.
- Hoods that pass containment tests at the factory but fail in the room.
See cross drafts, diffusers and supply air and fume hood energy use. With variable air volume systems, supply must track exhaust closely.