Glossary

Constant air volume (CAV)

A fume hood exhaust arrangement in which the hood draws the same airflow at all times, regardless of sash position.

In a constant air volume system, the exhaust fan and balancing dampers are set so each fume hood draws a fixed airflow. That flow is normally sized to reach the design face velocity with the sash at its working height. A bypass grille keeps face velocity from climbing too high when the sash is lowered.

The required flow follows a simple relationship: exhaust volume equals open face area times face velocity. For example, an opening of 0.7 m² at 0.5 m/s draws 0.35 m³/s (about 740 cfm).

Strengths of CAV:

  • Simple controls with few parts to fail.
  • Stable room pressure, since flows do not change.
  • Lower first cost and easier balancing.

The main drawback is energy. A CAV hood exhausts its full design flow 24 hours a day, open or closed. Every litre has to be replaced with conditioned outdoor makeup air, which is costly to heat through a Canadian winter. Labs with many hoods, long operating hours or high utility costs often look at VAV or high-performance low-flow hoods instead, and some existing CAV systems are converted to two-state control with separate occupied and unoccupied flows.

See Bypass, CAV and VAV fume hoods compared.