A VAV fume hood measures either the sash position or the airflow through a sensor in the hood's side wall, and a controller drives a fast-acting exhaust valve to match. As the sash comes down, exhaust flow drops while face velocity holds near its setpoint. The room's supply and general exhaust valves track those changes to keep the lab at its intended pressure relative to the corridor.
Even with the sash closed, a VAV hood keeps exhausting a minimum flow to dilute vapours inside the hood. That minimum is set by the design standard and the owner's EHS requirements.
Why choose VAV:
- Lower energy use when users close sashes, since less conditioned air is exhausted.
- Smaller fans, ducts and air handlers when the design applies a diversity factor.
What it demands:
- Careful commissioning, calibration and periodic checks of sensors, valves and response time.
- Users who actually close sashes. Savings depend on habits, so automatic sash closers and occupancy sensors are common add-ons.
- Reliable airflow monitors and alarms, which every hood should have anyway.
For a side-by-side comparison with constant-volume designs, see Bypass, CAV and VAV fume hoods compared.