In a building with variable air volume fume hoods, exhaust flow varies with sash position. It is unlikely that every hood will be fully open at the same moment, so engineers often size fans, ducts, air handlers and makeup air for a fraction of the theoretical maximum. That fraction is the diversity factor.
For example, 20 hoods that each need 500 L/s fully open would total 10,000 L/s. Designed at a diversity factor of 70%, the system would be sized for 7,000 L/s. The saving shows up in smaller equipment, smaller shafts and lower first cost.
The right factor depends on how the lab is used:
- Research labs where hoods are used intermittently can often justify diversity.
- Teaching labs, where a whole class may open every sash at once, usually need little or no diversity.
- Constant air volume systems have no diversity: every hood draws full flow all the time.
The risk is under-sizing. If more sashes are open than the design assumed, the system cannot maintain face velocity and hood alarms sound. Sash management, automatic sash closers and good airflow monitors protect the assumption, and the mechanical engineer of record should base the factor on real usage data where it exists.