Air changes per hour (ACH)

The volume of air supplied to or exhausted from a room in one hour, divided by the room's volume.

Air changes per hour express ventilation relative to room size. The calculation is simple: airflow in cubic metres per hour divided by room volume in cubic metres. For example, a lab 8 m by 6 m with a 3 m ceiling has a volume of 144 m³. Six air changes per hour is 864 m³/h, or 240 L/s (about 510 cfm).

In chemical labs, ACH sets a minimum dilution rate. Owners and design guides commonly specify minimums for occupied labs somewhere in the range of about 4 to 12 ACH, often with lower rates when the lab is unoccupied. In practice, fume hood exhaust or cooling load often drives total airflow above that minimum. Many institutions now set the rate through a risk assessment rather than a single fixed number.

In cleanrooms with non-unidirectional airflow, ACH is the main design lever for reaching an ISO class: higher rates dilute and remove particles faster, and rates rise sharply as the class gets cleaner. Pharmacy compounding standards set specific minimums, for example 30 ACH of HEPA-filtered air for an ISO 7 buffer room under USP <797>.

ACH is the wrong measure for unidirectional zones, where air velocity is specified instead.

See cleanroom HVAC and air change rates and pharmacy compounding cleanrooms.